Citel DS240S-280DC SPD, DC or type 2, PV network 280Vdc
DS240S-DC surge protectors are designed to protect equipment connected to DC (and AC) power supplies from lightning surges. It is based on varistors matched to the network voltage: the varistors have thermal disconnection devices to control any end-of-life. These SPD are DIN rail compatible and is connected in parallel on the line to be protected.
Features
- DC or PV power surge protector 280V DC
- Compact design Imax: 40 kA Pluggable module Remote signaling (option)
- Very low Up protection level
Electrical Specifications
SPD type (following IEC tests) 2
Network DC or PV network: 280V DC
Nominal DC voltage Un-dc: 280VDC
Nominal PV voltage Uocstc: 280VDC
Max. AC operating voltage L-N Uc: 275V AC
Max. PV operating voltage Ucpv: 350V DC
Max. DC operating voltage Uc: 350V DC
Max. load current IL: 20 A
Residual Current(Leakage current to Ground) Ipe: < 0.1 mA
PV Permanent Operating current
(Current consumption at Ucpv) Icpv: < 0.1 mA
Follow current If None
Nominal discharge current (15 x 8/20 µs impulses) In: 20 kA
Max. discharge current(max. withstand @ 8/20 µs by pole) Imax: 40 kA
Total Maximum discharge current
(max. total withstand @ 8/20 µs ) Imax Total: 80 kA
Current withstand short circuit PV Iscpv: 1000 A
Connection mode(s): +/-/PE
Protection mode(s): Common mode
Protection level +/PE (-/PE)(@ In (8/20µs)): Up 1200 V
Mechanical characteristics
Technology: MOV
SPD configuration: 2 poles
Connection to Network: By screw terminals: 1.5-10mm² (actives wires) and 2.5-25mm² (ground)
Format: Plug-in modular box
Mounting Symmetrical rail 35 mm (DIN 60715)
Housing material Thermoplastic UL94-V0
Operating temperature Tu: -40/+85°C
Protection rating: IP20
Failsafe mode: Disconnection from DC line
Disconnection indicator: 2 mechanical indicators
Spare module(s): DSM240-280DC
Remote signaling of disconnection: Option DS240S-280DC : output on changeover contact
Weight: 0.13 kg
Associated disconnectors
Thermal disconnector: internal
Fuses: Fuses type gG - 50 A